logo
  • English
Home ProductsAerial Bundled Cable ABC

LV PVC Fire Proof Aerial Bundled Cable ABC Overhead Electrical Cable for Power Transmission

Certification
China Zhongdong Cable Co., Ltd. certification
China Zhongdong Cable Co., Ltd. certification
I'm Online Chat Now

LV PVC Fire Proof Aerial Bundled Cable ABC Overhead Electrical Cable for Power Transmission

LV PVC Fire Proof Aerial Bundled Cable ABC Overhead Electrical Cable for Power Transmission
LV PVC Fire Proof Aerial Bundled Cable ABC Overhead Electrical Cable for Power Transmission

Large Image :  LV PVC Fire Proof Aerial Bundled Cable ABC Overhead Electrical Cable for Power Transmission

Product Details:
Place of Origin: Hebei,China
Brand Name: Zhongdong
Certification: CCC,ISO,TUV,CE
Model Number: ABC
Payment & Shipping Terms:
Minimum Order Quantity: Negotiable
Price: Negotiable
Packaging Details: Wooden Drum/ Steel Drum
Delivery Time: 7-30 days based on different qty
Payment Terms: ,L/C,T/T
Supply Ability: 100KM/Week

LV PVC Fire Proof Aerial Bundled Cable ABC Overhead Electrical Cable for Power Transmission

Description
Application: Overhead Distribution Line Cores Nos: 1,2,3,4 More Multicore
Rated Voltage: 0.6/1 KV Installation Degree: -20℃-90℃
Neutral Messengers: AAC Or ACSR Insulation: XLPE/PE/PVC
Highlight:

Fire Proof Aerial Bundled Cable ABC

,

Power Transmission Overhead Electrical Cable

Low Voltage PVC Fire Proof Aerial  Bundled Cable ABC Overhead Electrical Lines for Power Transmission

 

 

Applicatiom

 

Low voltage aerial cable is designed to supply 600/1000-volt aerial service for temporary service at construction sites, as a service drop (power pole to service entrance), as a secondary cable (pole to pole) or street lighting. This over-head cable provides reinforced insulation acc.

 

Characteristics


Voltage rating: 1kV
Test voltage: 4kV, 5min no breakdown.


Operating temperature

 

PVC: -15°C to +70°C
PE: -40°C to +70°C
XLPE : -40°C to +90°C

Minimum laying/ installation temperature


PVC: 0°C PE: -20°C XLPE: -20°C
Note: The above temperature rating provisions can be changed as order.

Minimum bending radius


12 x OD (overall diameter)

 

Specification

 

 

Cable Dimensions of Aluminum Conductor Aerial Overhead Wires

Nominal Cross
Section Area
(mm2)

Max. DC Resistance of
Conductor in Bundle at 20ºC
(Ohms/km)

Current Carrying Capacity
in Free Air
(AMPS)

Minimum Tensile
Strength of Conductor
(kN)

25

1.2

107

4.1

35

0.868

132

5.6

50

0.641

165

7.6

70

0.443

205

11.0

95

0.320

258

15.3

120

0.253

300

19.4

 

Contact Details
Zhongdong Cable Co., Ltd.

Contact Person: Mr. Bai

Tel: +8619829885532

Send your inquiry directly to us (0 / 3000)